32A |
40A |
80A |
---|---|---|---|
Output power |
32A max 7.7 kW at 240V 1-phase
|
40A max 9.6 kW at 240V 1-phase
|
80A max 19.2 kW at 240V 1-phase
|
Circuit requirements |
40 amp 2-pole breaker
|
50 amp 2-pole breaker
|
100 amp 2-pole breaker
|
Recommended wiring |
#8WG or larger gauge copper wires for the conductors (NEC 625.17(A)(2) #10AWG green or bare copper for the ground conductor (no NEU)
|
#6WG or larger gauge copper wires for the conductors (NEC 625.17(A)(2) #10AWG green or bare copper for the ground conductor (no NEU)
|
#2 or 3AWG or larger gauge copper wires for the conductors (NEC 625.17(A)(2) #6AWG green or bare copper for the ground conductor (no NEU)
|